Red Emergency Stop Button Wiring (LA38): NC, NO and 12V

Cartoon of a red LA38 emergency stop button with white arrows and a yellow collar, wired in the red positive wire that feeds a black 12V fan

Quick answer: a red emergency stop button goes in the power wire, not on an Arduino pin. Use the NC (normally closed) pair, terminals 11 and 12, in series with the load’s 12V positive wire. A press opens the contact and the load loses power, whatever the code is doing.

  1. 12V (+) to terminal 11. Terminals 11 and 12 are at opposite ends of the block, not side by side.
  2. Terminal 12 to the load’s (+) wire, or to relay COM if a relay switches the load.
  3. Load (-) straight back to 12V (-).
  4. Press to stop. Twist the head the way the arrows point to release.
  5. The NO pair (23 and 24) is spare, for a status signal to an Arduino.

12V DC only on this page.

NC and NO on the LA38 contact block

The LA38 emergency stop button’s contact block holds two separate switches. NC (normally closed) conducts while the head is up and opens on a press. NO (normally open) does the reverse.

An emergency stop puts NC in series with the load. Follow the current: out of the supply’s 12V (+), into terminal 11, across the closed contact, out at terminal 12, through the fan and back to the supply’s (-). It is one path with no branch, so the fan runs only while every part of it conducts.

A press lifts the contact’s moving piece off its fixed points. The path now has an air gap and the current stops. A loose screw or a cut wire opens the same path, so those faults stop the fan too. An NO contact would have to close to send a stop, so a broken wire there would look like nobody pressing. No code sits in this loop, so a hung sketch cannot keep the fan running.

Cartoon of a single wire loop running from a black supply board through a red emergency stop button to a spinning black fan and back, with arrows showing the current's path
One loop: 12V leaves the supply board, passes through the button’s NC contact, runs the fan and returns. Open the loop anywhere and the fan stops.

Parts you need

Parts list

ItemPriceQty
Arduino Uno Compatible SMD UNO R3 with Type B Cable - ATMEGA328P with CH340G-Microcontroller ProjectArduino Uno Compatible SMD UNO R3 with Type B Cable - ATMEGA328P with CH340G-Microcontroller ProjectUNOCH34RM22.90
Relay Module 3.3V 5V 12V 1/2/4/8 Ways Optocoupler Trigger Relay Module 1 2 4 8 Channel Relay Module - 5V RELAY MODULE(1WAY)Relay Module 3.3V 5V 12V 1/2/4/8 Ways Optocoupler Trigger Relay Module 1 2 4 8 Channel Relay Module - 5V RELAY MODULE(1WAY)1WRELAYRM3.15
XL830L Digital Multimeter with backlight Portable Multimeter Electronics ProjectXL830L Digital Multimeter with backlight Portable Multimeter Electronics ProjectMULTIMERM25.95
Industrial Emergency Momentary Button LA38 Push Switch RED Push To Stop Button - MOMENTARY BUTTONIndustrial Emergency Momentary Button LA38 Push Switch RED Push To Stop Button - MOMENTARY BUTTONRMOMENBRM9.95

Add the Uno and relay module only if a sketch already switches your load. The multimeter confirms the NC pair and the 12V polarity. The flat-head momentary button is the sibling to pick when the load should be off only while your finger is on it.

The 12V 2A adapter has a UK 3-pin plug for a Malaysian 13A socket (230V, 50Hz). It plugs into the multi-voltage supply board. The board’s two regulators only make the 5V and 3.3V pins, so its red +12V pins are the adapter’s 12V passed straight through, up to the board’s 1A limit.

The 80 mm fan stands in for your load. A 12V pump or brushed motor wires the same way.

Step 1: Find terminals 11 and 12

The LA38 emergency button‘s contact block has four screws under its clear cover, two at each end. White numbers name them: 24 and 12 at one end, 23 and 11 at the other.

The last digit says what kind of contact it is: 1 and 2 mark normally closed, 3 and 4 normally open. The first digit says which contact. So 11-12 is the NC pair and 23-24 the NO pair.

Each pair runs from one end of the block to the other. The two screws side by side, such as 12 and 24, belong to different contacts with nothing joining them. Wire across those two and the fan never runs.

Confirm with a multimeter on continuity (see our multimeter guide) before wiring:

Probes on Head up Head pressed What it is
11 and 12 Beeps Silent NC: the pair for the stop
23 and 24 Silent Beeps NO: spare, for a status signal
12 and 24 (side by side) Silent Silent Two different contacts
Cartoon close-up of an orange and clear LA38 contact block with four silver screws, a red lane and a green lane running end to end, and a cross between two neighbouring screws
Each contact runs from one end of the block to the other. The two screws side by side belong to different contacts. Read the printed numbers to tell which lane is NC.

Step 2: Wire the button into the 12V positive line

12V DC only. The 660V on the LA38’s cover is an insulation rating. Putting an emergency stop into 230V wiring is work for a registered wireman.

Check the supply first: with the adapter plugged in and in the board’s jack, measure DC volts from a red +12V pin (red probe) to a black GND pin. Expect about 12V with no minus sign. A minus sign means reversed polarity: stop there. Unplug the adapter, then wire:

From To Jumper
Supply board, any red +12V pin Terminal 11 Male-to-female: socket on the pin, metal pin under the screw
Terminal 12 Fan plug, the socket on the red wire Male-to-male: one pin under the screw, one in the plug
Fan plug, the socket on the black wire Supply board, any black GND pin Male-to-female: pin in the plug, socket on the GND pin

At each terminal, loosen the screw (small cross-head screwdriver), slide the jumper’s pin fully under the square plate, tighten and tug. Tape any jumper that sits loose in the fan’s white plug to the fan lead.

Step 3: Press to stop, twist to release

Plug the adapter in last, with the red head up, and check:

You do What should happen Why
Plug in, head up The fan runs The NC contact is closed
Press the head It clicks down and the fan coasts to a stop The NC contact opens
Let go The fan stays off A catch inside the head holds it down
Twist the head the way the three white arrows point (clockwise) The head pops up and the fan runs again A spring returns the head and the contact closes

If it does something else:

What you see Cause Fix
The fan never runs and the head sits low The head is still latched down (pressed during the Step 1 test, or in handling) Twist it the way the arrows point until it springs up
The fan never runs, head up The wires are on two side-by-side screws, or a pin is not under its plate Move them to 11 and 12, one at each end of the block
The fan runs only while the head is down The wires are on 23 and 24, the NO pair Move them to 11 and 12
The fan runs and pressing does nothing The button is not in the loop: the fan’s red wire goes straight to +12V Pass that wire through 11 and 12
The fan stutters or stops when you touch a wire A jumper is loose in the fan’s white plug, on a supply pin or under a screw Push it fully home, retighten the screw and tape the plug to the fan lead

In this no-code build the fan restarts the moment the head pops up. On anything that can hurt someone, resetting an emergency stop must not restart the machine by itself. Whoever twists the head may not see a hand still inside, so a separate start action should restart it. The Arduino section adds one.

Cutting power is no brake. An arm or a vertical axis held up only by its motor can drop the moment the power goes.

Emergency button or momentary button: which one do you need?

The LA38 comes in two versions, each with a different red head on the same contact block (11-12 NC, 23-24 NO).

Emergency button Momentary button
Head Red mushroom with three white arrows, on a yellow collar Flat red face inside a silver ring
When you let go Stays down until you twist it (latching) Springs back up
Load on 11-12 Off from the press until the twist Off only while your finger is on it
Panel hole 22 mm 22 mm
Pick it for Stopping a robot, conveyor or mini CNC and keeping it stopped A pause button, or a start or signal button on the NO pair

One buyer who had ordered a different switch wrote to us: “saya mahu suis off bila di tekan..betul tak suis yg saya order ni”, then “Saya nk yang LA38..macamana mau tukar order tu boss.. Sebab mau off bila ditekan”. A switch that goes off when pressed means the NC pair, and both heads have it. Pick by what should happen when you let go.

Cartoon of two LA38 buttons side by side: a red mushroom emergency stop with white arrows and a yellow collar, and a flat red momentary button in a silver ring
Same contact block, different heads. The mushroom head latches and is twisted to release. The flat head springs back when you let go.

Arduino emergency stop: where the button goes with a relay

An Arduino emergency stop keeps the LA38 in the 12V line. The Uno switches the fan through a relay module and reports the stop. Our relay module guide covers the relay’s control wires and trigger jumper.

From To Jumper Job
Uno 5V, GND, D7 Relay DC+, DC-, IN Male-to-male Relay control, as in the relay guide. The Uno runs from its USB cable
Supply board +12V pin Terminal 11 Male-to-female 12V into the button
Terminal 12 Relay COM Male-to-male 12V reaches the relay only through the NC contact
Relay NO Fan plug, red-wire socket Male-to-male The sketch’s on/off switch
Fan plug, black-wire socket Supply board GND pin Male-to-female Return path
Terminal 23 Uno D2 Male-to-male Status. INPUT_PULLUP holds D2 HIGH while the head is up. A press closes 23-24 and ties D2 to GND, so it reads LOW (pull-ups are explained in our push button guide)
Terminal 24 Uno GND (the Uno has three GND sockets) Male-to-male Status return. The block’s two contacts are electrically separate, so this 5V circuit never meets the 12V on 11-12

Where the button sits decides what a press can do:

Button position What a press breaks Limits
In the load’s (+) wire, before the relay (this build) The full load current Works even if the relay contact sticks or the sketch hangs. The button must be able to break the load’s current
In the relay coil’s supply (the wire to DC+) Only the coil current: 5V across the SRD-05VDC-SL-C’s 70 Ω coil is about 71 mA. The relay’s spring then opens the load contact For loads bigger than the button should break. No help if the relay contact has welded shut
On an Arduino input only Nothing A status signal, never the stop
// LA38 emergency stop + relay module on an Arduino Uno: status and restart lock.
// The stop itself is wiring, not code: 12V (+) -> terminal 11 -> terminal 12 -> relay COM.
// This sketch only reports the press and keeps the relay off after the release.
//   D7 -> relay IN, 5V -> DC+, GND -> DC-
//   D2 -> terminal 23, GND -> terminal 24 (NO pair: closed while the head is down)

const int RELAY_PIN = 7;
const int ESTOP_PIN = 2;

// Match these to the relay module's trigger jumper, as in the relay guide:
// jumper on L = LOW / HIGH, jumper on H = HIGH / LOW.
const int RELAY_ON  = LOW;
const int RELAY_OFF = HIGH;

const unsigned long RELEASE_HOLD_MS = 50;  // ignore contact bounce on release

bool stopped = false;         // once true, only a reset of the Uno clears it
                              // (opening the Serial Monitor resets the Uno too)
bool releaseTold = false;
unsigned long lastPressedMs = 0;

void setup() {
  digitalWrite(RELAY_PIN, RELAY_OFF);  // define OFF before the pin drives
  pinMode(RELAY_PIN, OUTPUT);
  pinMode(ESTOP_PIN, INPUT_PULLUP);    // HIGH = head up, LOW = head pressed
  Serial.begin(9600);

  if (digitalRead(ESTOP_PIN) == LOW) {
    stopped = true;                    // never start with the head down
    Serial.println(F("E-STOP is pressed. Relay stays off."));
  } else {
    digitalWrite(RELAY_PIN, RELAY_ON);
    Serial.println(F("Running. Relay on."));
  }
}

void loop() {
  bool pressed = (digitalRead(ESTOP_PIN) == LOW);

  if (pressed) {
    lastPressedMs = millis();
    releaseTold = false;
    if (!stopped) {
      stopped = true;                  // latch the stop
      digitalWrite(RELAY_PIN, RELAY_OFF);
      Serial.println(F("E-STOP pressed. Relay off."));
    }
  } else if (stopped && !releaseTold &&
             millis() - lastPressedMs >= RELEASE_HOLD_MS) {
    releaseTold = true;
    Serial.println(F("Head released. Still off: press RESET on the Uno to run again."));
  }
}

The sketch switches the relay on at power-up only if the head is up. A press switches it off and latches the stop. Twist the head and 12V is back at COM, but the relay stays open until you press the Uno’s RESET button. Open the Serial Monitor before you test: opening it resets the Uno and, with the head up, restarts the fan.

D2 is status only. If that wire breaks, the fan restarts on release, but the press still cuts it through 11-12.

Will Donaldson wires an NC/NO emergency stop and relays into his robot, OMNi:

What does the 10A on the contact block mean?

The LA38 contact block is marked Ith 10A and Ui AC660V, the same figures as the LA38 family datasheet. Ith is the conventional thermal current: what the closed contact can carry continuously without overheating. Ui is the voltage its insulation is built for. Neither is the current the contact can switch off.

As the contact opens under load, the current keeps flowing for a moment as an arc across the gap, and each arc burns a little metal away. AC at 50Hz falls to zero 100 times a second, which lets the arc die. DC never does, so its arc lasts until the gap is wide enough. A motor, pump or solenoid is worse: the collapsing magnetic field in its coil keeps pushing current.

So match the button’s position to the load:

Load Where the button goes Also
This build’s fan: a fraction of an amp (read the current on the fan’s label), through a board limited to 1A In the load’s (+) wire Jumper leads are enough
A motor drawing several amps In the coil circuit of a relay or contactor, which breaks the load current. Switching a coil is the duty the block’s AC-15 and DC-13 marks describe: they are the IEC classes for electromagnet loads Wire thicker than jumper leads on the load side
A brushed motor, pump or solenoid of any size As above, by its current A flyback diode across the load gives the coil’s current a path other than the arc. Our 12V solenoid lock guide shows how

FAQ

Which terminals do I use on an LA38 emergency stop button?

Terminals 11 and 12, the normally closed pair, in series with the load’s positive wire.

Can I wire an emergency stop button to an Arduino pin only?

Only as a status signal. A pin can only ask the sketch to stop, and a hung sketch cannot answer. Put the NC pair in the load’s power wire.

Can I use this emergency stop button on 230V mains or a real machine?

Not with this guide’s wiring. It is a 12V DC stop for hobby and school projects. Mains wiring is work for a registered wireman. A machine that can injure someone needs a designed safety circuit: an emergency stop device built to ISO 13850 and IEC 60947-5-5 with direct-opening contacts, plus a safety relay.

Last updated November 2026. Stuck? Chat with us on WhatsApp.